Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table U. Power Cable Conduit Requirements Powerware 9330 (35 kVA--40 kVA)
Powerware
System
Voltage
Terminal
Number of
Wires in
Conduit
Minimum
Conduit
Trade Size
(inches)
Number of
Conduits
AC Input to UPS
(A, B, C, Gnd)
4
1-1/4
1
9330-40/35
208
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
2
1
AC
Output
(A, B, C, Neut, Gnd)
5
2
1
AC Input to UPS
(A, B, C, Gnd)
4
1
1
9330---40/35
480
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1
1
C
Output
(A, B, C, Neut, Gnd)
5
1
1
AC Input to UPS
(A, B, C, Gnd)
4
3/4
1
9330---40/35
600
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
3/4
1
C
Output
(A, B, C, Neut, Gnd)
N/A
N/A
N/A
9330---40/35
288
DC
External Battery DC Source
(Positive, Negative, Gnd)
3
1
1
AC Input to UPS
(A, B, C, Gnd)
4
1-1/2
1
9330-40/40
208
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
2
1
C
Output
(A, B, C, Neut, Gnd)
5
2
1
AC Input to UPS
(A, B, C, Gnd)
4
3/4
1
9330-40/40
480
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
1
1
C
Output
(A, B, C, Neut, Gnd)
5
1
1
AC Input to UPS
(A, B, C, Gnd)
4
3/4
1
9330-40/40
600
AC
AC Input to Bypass
(A, B, C, Neut, Gnd)
5
3/4
1
C
Output
(A, B, C, Neut, Gnd)
N/A
N/A
N/A
9330---40/40
288
DC
External Battery DC Source
(Positive, Negative, Gnd)
3
1-1/4
1