DESCRIPTION:
DATE:
DRAWING NO:
10 of 17
SHEET:
REVISION: F
111501
NOTE: Customer ground, size 1/0, can be
run in any conduit listed in Table R.
POWER WIRING INSTALLATION NOTES
164201300---1
A---11
Powerware 9330 (10 kVA--40 kVA) Installation and Operation
164201300 REV. G 061502
Table O. UPS Cabinet Power Cable Terminations Powerware 9330 (25 kVA---40 kVA)
Terminal Function
Terminal
Function
Size of Pressure
Termination
Vendor
Tightening Torque
N-M (lb-in.)
Type
Screw
AC Input to UPS
A
Phase A 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
p
Rectifier and Bypass
(TB2)
A
Phase A 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
(TB2)
(Single Input)
B
Phase B 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
(Single Input)
B
Phase B 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
C
Phase C 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
C
Phase C 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
N
Neutral
1
#4 #4/0
Entrelec
4-6(35-52)
6 mm
N
Neutral
1 --- #4---#4/0
Phoenix
15-20(133-177)
6 mm
Allen
AC Input to UPS
C
A
Phase A 1 --- #2---#4/0
ABB
13.5(120)
3/16 i
p
Rectifier (CB1)
(Dual Input)
B
Phase B 1 --- #2---#4/0
ABB
13.5(120)
3/16 in.
Allen
(Dual Input)
C
Phase C 1 --- #2---#4/0
ABB
13.5(120)
Allen
AC Input To Bypass
A
Phase A 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
p
yp
(TB2)
(Dual Input)
A
Phase A 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
(Dual Input)
B
Phase B 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
B
Phase B 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
C
Phase C 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
C
Phase C 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
N
Neutral
1
#4 #4/0
Entrelec
4-6(35-52)
6 mm
N
Neutral
1 --- #4---#4/0
Phoenix
15-20(133-177)
6 mm
Allen
AC Output to Critical
A
Phase A 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
p
Load
(Part of TB3)
A
Phase A 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
(Part of TB3)
B
Phase B 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
B
Phase B 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
C
Phase C 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
C
Phase C 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
N
Neutral
1
#4 #4/0
Entrelec
4-6(35-52)
6 mm
N
Neutral
1 --- #4---#4/0
Phoenix
15-20(133-177)
6 mm
Allen
DC Input from
Battery to UPS
N/A
Battery
(+)
Red Battery
Connector
N/A
N/A
N/A
Battery to UPS
N/A
Battery
(---)
Black Battery
Connector
N/A
N/A
N/A
External Battery
S
Battery
Positive
1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
y
Input to UPS
(Part of TB3)
Battery
+
Positive
1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
(Part of TB3)
Battery
Negative 1
#14 #0
Entrelec
2.5-2.9(22-26)
Slotted
Battery
---
Negative 1 --- #14---#0
Phoenix
3.2-3.7(28-33)
Slotted
Customer Ground
Ground
Ground
2 --- #14---1/0
N/A
5.6 (50)
Slotted