Advanced Analog Alarm Settings
The advanced Analog Alarm Settings window expands the basic alarm settings options to up to five
severity levels.
Configure the following parameters:
Send Syslog Alert
When enabled, sends a message to syslog when an alarm is triggered or
cleared. The syslog entry includes the severity level and the value that caused
the alarm to trigger or clear. The syslog message is associated with
Level
Critical
.
Default: Disabled
Send SNMP Alert
When enabled, sends an SNMP trap when an alarm is triggered or cleared. The
trap consists of the severity level and whether the alarm was triggered or
cleared.
Default: Disabled
Trigger Type
If the
Trigger Type
is
Low
, an alarm is triggered when the input drops below
the specified
Trigger
value; other severity level trigger values must decrease in
value with each subsequent level. If the
Trigger Type
is
High
, an alarm is
triggered when the input is higher than the specified
Trigger
value; other
severity level trigger values must increase in value with each subsequent level.
Clear Mode
To clear an alarm, the input must drop below the specified value when
Trigger
Type
is
High
or go above the specified value when
Trigger Type
is
Low
.
Level 1-5
Defines the Level severity settings for up to five levels. If the
Trigger Type
is
Low
, an alarm is triggered when the input drops below the specified
Trigger
value; other severity level trigger values must decrease in value with each
subsequent level. If the
Trigger Type
is
High
, an alarm is triggered when the
input is higher than the specified
Trigger
value; other severity level trigger
values must increase in value with each subsequent level.