Field descriptions – Perle Systems 5500161-40 User Manual
Page 262
Channels
262
IOLAN SDS/SCS/STS/MDC User’s Guide, Version 4.0
Field Descriptions
Configure the following parameters:
Description
Provide a description of the channel, making it easier to identify.
Data Options: Maximum 20 characters, including spaces
Output
Specify how the channel output will be handled.
Data Options:
z
Manual—You must manually manipulate the channel output.
z
Pulse—Activates and deactivates the channel output activity in intervals
after it is manually activated.
z
Inactive-to-Active Delay—The channel output will remain inactive for
the specified time interval after it is manually started.
z
Active-to-Inactive Delay—The channel output will go inactive after the
specified time interval after it is manually started.
Default: Manual
Pulse Mode
When
Output
is set to
Pulse
, you can specify the manner of the pulse.
Data Options:
z
Continuous—Continuously pulses active and inactive.
z
Count—Pulses an active/inactive sequence for the specified number of
times.
Default: Continuous
Pulse Count
The channel output will pulse for the specified number of times; each count
consists of an active/inactive sequence.
Default: 1
Inactive Signal
Width
How long the channel will remain inactive during pulse mode.
Range: 1-9999 x 100 ms
Default: 1 (100 ms)