Temperature

Temperature input channels monitor RTD or thermocouple temperature sensors inputs for the most
common ranges. You can also configure severity alarms that can send an email, a syslog message,
and/or an SNMP trap when an alarm is triggered or cleared; See

Alarm Settings on page 271

for

more information about the alarms.

RTD ranges are:

z

Pt100 a=385 -50 to 150C

z

Pt100 a=392 -50 to 150C

z

Pt1000 a=385 -40 to 160C

z

Pt100 a=385 0 to 100C

z

Pt100 a=392 0 to 100C

z

NiFe604 a=518 -80 to 100C

z

Pt100 a=385 0 to 200C

z

Pt100 a=392 0 to 200C

z

NiFe604 a=518 0 to 100C

z

Pt100 a=385 0 to 400C

z

Pt100 a=392 0 to 400C

z

Pt100 a=385 -200 to 200C

z

Pt100 a=392 -200 to 200C

Note:

IEC RTD 100 ohms.=0.00385
JIS RTD 100 ohms.=0.00392

Thermocouple ranges are:

z

B 500 to 1800C

z

K 0 to 1370C

z

T -100 to 400C

z

E 0 to 1000C

z

R 500 to 1750C

z

J 0 to 760C

z

S 500 to 1750C

In the following example, a Temperature I/O IOLAN is used to monitor industrial freezer temperature
sensors, with an alarm set to send a syslog message if the temperature rises above 31

o

C.

IOLAN

pe

rl

e

Monitoring

Application

Network

Industrial
Freezers

Temperature I/O

T4