beautypg.com

Powerware 5140 User Manual

Page 62

background image

Specifications

54

Powerware

®

5140 User’s Guide

:

www.powerware.com

Table 6. Weights and Dimensions

UPS

Extended Battery Module

Power Distribution Unit

Dimensions (WxDxH)

17.3

2 x 24.32 x 10.52 (6U)

(43.8 cm x 61.7 cm x 26.7 cm)

17.3

2 x 22.52 x 5.252 (3U)

(43.8 cm x 57.2 cm x 13.3 cm)

19.3

2 x 9.92 x 22

(49 cm x 25.2 cm x 5 cm)

Weights

Chassis: 110 lb (50 kg)

Battery Tray: 70 lb (32 kg)

Total: 250 lb (114 kg)

Chassis: 35 lb (16 kg)

Battery Tray: 70 lb (32 kg)

Total: 175 lb (80 kg)

19 lb (8.6 kg)

Table 7. Environmental and Safety

Operating Temperature

10°C to 40°C (50°F to 104°F)

Long term use at ambient greater than 25°C (77°F) reduces battery life.

Transit Temperature

-20°C to 55°C (-4°F to 131°F)

Storage Temperature

0°C to 25°C (32°F to 77°F)

Relative Humidity

Operating: 20-80% noncondensing

Non-operating: 5-95% noncondensing

Operating Altitude

Up to 10,000 feet above sea level

Transit Altitude

Up to 30,000 feet above sea level

Audible Noise

Less than 55 dBA typical

Surge Suppression

IEEE 587/ANSI C62.41 Category B

Safety Conformance

UL 1778; CAN/CSA C22.2, No. 107.1, No. 107.2, No. 950

EN 50091-1-1, EN 60950

Safety Markings

PW5140 6000: UL, CSA

PW5140 6000i and PW5140 6000 HW: UL, CSA, VDE, CE

EMC

FCC Part 15 Class A; EN 50091-2; CISPR 22, Class A

Table 8. Battery

Voltage, Size

12V, 5 Ah

Type

Sealed, maintenance-free, valve-regulated, lead-acid

Charging

Internal batteries: approximately 3 hours to 80% usable capacity at nominal line voltage
Extended Battery Modules: approximately 10 hours to 80% usable capacity at nominal line
voltage