Specifications
54
Powerware
®
5140 User’s Guide
:
www.powerware.com
Table 6. Weights and Dimensions
UPS
Extended Battery Module
Power Distribution Unit
Dimensions (WxDxH)
17.3
2 x 24.32 x 10.52 (6U)
(43.8 cm x 61.7 cm x 26.7 cm)
17.3
2 x 22.52 x 5.252 (3U)
(43.8 cm x 57.2 cm x 13.3 cm)
19.3
2 x 9.92 x 22
(49 cm x 25.2 cm x 5 cm)
Weights
Chassis: 110 lb (50 kg)
Battery Tray: 70 lb (32 kg)
Total: 250 lb (114 kg)
Chassis: 35 lb (16 kg)
Battery Tray: 70 lb (32 kg)
Total: 175 lb (80 kg)
19 lb (8.6 kg)
Table 7. Environmental and Safety
Operating Temperature
10°C to 40°C (50°F to 104°F)
Long term use at ambient greater than 25°C (77°F) reduces battery life.
Transit Temperature
-20°C to 55°C (-4°F to 131°F)
Storage Temperature
0°C to 25°C (32°F to 77°F)
Relative Humidity
Operating: 20-80% noncondensing
Non-operating: 5-95% noncondensing
Operating Altitude
Up to 10,000 feet above sea level
Transit Altitude
Up to 30,000 feet above sea level
Audible Noise
Less than 55 dBA typical
Surge Suppression
IEEE 587/ANSI C62.41 Category B
Safety Conformance
UL 1778; CAN/CSA C22.2, No. 107.1, No. 107.2, No. 950
EN 50091-1-1, EN 60950
Safety Markings
PW5140 6000: UL, CSA
PW5140 6000i and PW5140 6000 HW: UL, CSA, VDE, CE
EMC
FCC Part 15 Class A; EN 50091-2; CISPR 22, Class A
Table 8. Battery
Voltage, Size
12V, 5 Ah
Type
Sealed, maintenance-free, valve-regulated, lead-acid
Charging
Internal batteries: approximately 3 hours to 80% usable capacity at nominal line voltage
Extended Battery Modules: approximately 10 hours to 80% usable capacity at nominal line
voltage