53
Powerware
®
5140 User’s Guide
:
www.powerware.com
C H A P T E R
8
S
PECIFICATIONS
This section provides the following specifications for the Powerware
5140 models:
: Electrical input and output
: Weights and dimensions
: Environmental and safety
: Battery
Table 4. Electrical Input
Nominal Voltage
Auto-sensing 208/230V default;
200, 208, 220, 230, 240V selectable
Voltage Range
±20% at full load for 208/220/230/240V nominal input voltage
+20%/–17% at full load for 200V nominal input voltage
166-288V at full load for 230V optional extended range
Nominal Frequency
50/60 Hz ±3 Hz
(+5/-3 Hz for 230V extended)
Connections
Hardwired Terminal Block
Table 5. Electrical Output
Power Levels (rated at
nominal inputs)
6000 VA, 6000W
Regulation Online
±10% of nominal voltage
+10% to -15% in extended voltage range
Nominal Output Voltage
On-Battery
230V for 220, 230, 240V settings
204V for 200, 208V settings
Output Voltage
Regulation On-Battery
±5% of nominal on-battery output voltage
Voltage Waveform
Normal mode: same as utility
On-Battery: sine wave
Overcurrent Protection
Resettable circuit breakers
Output Connections
PW5140 6000: Two L6-30 and Two IEC-320-C13
PW5140 6000i: Twelve IEC-320-C13 and Three IEC-320-C19
PW5140 6000 HW: Hardwired and Two IEC-320-C13