beautypg.com

Powerware 5140 User Manual

Page 38

background image

Installation

30

Powerware

®

5140 User’s Guide

:

www.powerware.com

8. Attach the battery front panel to the chassis using the attached

screws.

Figure 21. Attaching the Battery Front Panel

9. Switch the main utility breaker on.

The UPS conducts a self-test and enters Standby mode,
indicated by the blinking



indicator.

10. Press the UPS On button.

The load segments cycle through a startup sequence and the
UPS enters Normal mode.

NOTE The batteries charge to 90% capacity in approximately 4 hours. However, it is
recommended that the batteries charge for 24 hours after installation or long storage.

11. If you installed an optional EBM, access the System Setup menu

and set the amp/hour rating for each EBM (see “Set Hardware
Configuration” on page 40).