Set voltage, Set site fault, Set sleep mode – Powerware 5140 User Manual

Page 50

background image

Front Panel Menus

42

Powerware

®

5140 User’s Guide

:

www.powerware.com

Set Voltage

Use the Set Voltage option to configure the UPS utility voltage. Use

?

and

+

to scroll through the values. An asterisk (*) shows the

current configuration.

Select the appropriate utility voltage range (use Table 1 to help select
the appropriate voltage):
: 200V
: 208V
: 220V
: 230V
: 240V
: 208/230V Auto-sensing
: 230V Extended (-35% to +20%)

Table 1. Nominal Input Voltage Ranges

Nominal Input

Voltage (Vac)

Normal Input

Voltage Range

Extended Input

Voltage Range

200V Nominal +20%/–17%

166-240V

208V Nominal ±20%

166-248V

220V Nominal ±20%

176-264V

230V Nominal ±20%

184-276V

166-288V

240V Nominal ±20%

192-288V

Set Site Fault

Use the Set Site Fault option to enable or disable the site wiring fault
alarm. The default is disabled. Enable the alarm for installations where a
grounded-neutral electrical system is in place (see “Site Fault Wiring”
on page 57 for more information).

Set Sleep Mode

Use the Sleep Mode feature to control loads that use less than 10% of the
current when the UPS is on battery. The default is disabled.

Enable this option if you do not want a load less than 10% of the current
to be protected by battery power. This feature conserves battery power
by shutting down less critical loads.