6 Troubleshooting

Issue 03/01

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

84

6SE6400-5CA00-0BP0

5: Identified main reactance less than 50 % and greater than 500 %

6: Identified rotor time constant less than 10 ms or greater than 5 s

7: Identified total leakage reactance less than 5 % and greater than 50 %

8: Identified stator leakage reactance less than 25 % and greater than 250 %

9: Identified rotor leakage inductance less than 25 % and greater than 250 %

20: Identified IGBT on-voltage less than 0.5 V or greater than 10 V

30: Current controller at voltage limit

40: Inconsistency of identified data set, at least one identification failed

Percentage values based on the impedance Zb = Vmot,nom / sqrt(3) / Imot,nom

Diagnose & Remedy

Fault value = 0: Check that the motor is connected to the inverter

Fault value = 1-40:

Check if motor data in P0304 to P0311 are correct

Check what type of motor wiring is required (star, delta).

F0042 Speed Control Optimisation Failure

OFF2

Possible Causes

Speed control optimisation (P1960) failed
Fault value = 0: Time out waiting for stable speed

= 1: Inconsistent readings

F0051 Parameter

EEPROM

Fault

OFF2

Possible Causes

Read or write failure while saving non-volatile parameter

Diagnose & Remedy

Factory Reset and new parameterization

Contact Customer Support / Service Department

F0052 Power stack Fault

OFF2

Possible Causes

Read failure for power stack information or invalid data

Diagnose & Remedy

Hardware defect, contact Customer Support / Service Department

F0053 IO EEPROM Fault

OFF2

Possible Causes

Read failure for IO EEPROM information or invalid data

Diagnose & Remedy

Check data

Change IO board

F0054 Wrong IO Board

OFF2

Possible Causes

Wrong IO board is connected

No ID detected on IO board, no data

Diagnose & Remedy

Check data

Change IO board

F0060 Asic

Timeout

OFF2

Possible Causes

Internal communications failure

Diagnose & Remedy

If fault persists, change inverter

Contact Service Department

F0070 CB setpoint fault

OFF2

Possible Causes