Siemens MICROMASTER 411 User Manual
Page 74
5 System Parameters
Issue 03/01
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
74
6SE6400-5CA00-0BP0
ParNr ParText
Default
Acc
WS
QC
P1060[1] JOG
ramp-up
time
10.00 2 CUT
N
P1061[1]
JOG ramp-down time
10.00
2
CUT
N
P1070[1]
CI: Main setpoint
755:0
3
CT
N
P1071[1]
CI: Main setpoint scaling
1:0
3
CT
N
P1075[1]
CI: Additional setpoint
755:1
3
CT
N
P1076[1]
CI: Additional setpoint scaling
1:0
3
CT
N
r1078
CO: Total frequency setpoint
-
3
-
-
r1079
CO: Selected frequency setpoint
-
3
-
-
P1080[1] Min.
frequency
0.00 1 CUT
Q
P1082[1] Max.
frequency
50.00 1 CT Q
P1091[1]
Skip frequency 1
0.00
3
CUT
N
P1092[1]
Skip frequency 2
0.00
3
CUT
N
P1093[1]
Skip frequency 3
0.00
3
CUT
N
P1094[1]
Skip frequency 4
0.00
3
CUT
N
P1101[1]
Skip frequency bandwidth
2.00
3
CUT
N
r1114
CO: Freq. setp. after dir. ctrl.
-
3
-
-
r1119
CO: Freq. setpoint before RFG
-
3
-
-
P1120[1] Ramp-up
time
10.00 1 CUT
Q
P1121[1] Ramp-down
time
10.00 1 CUT
Q
P1130[1]
Ramp-up initial rounding time
0.00
2
CUT
N
P1131[1]
Ramp-up final rounding time
0.00
2
CUT
N
P1132[1]
Ramp-down initial rounding time
0.00
2
CUT
N
P1133[1]
Ramp-down final rounding time
0.00
2
CUT
N
P1134[1] Rounding
type
0
2 CUT
N
P1135[1]
OFF3 ramp-down time
5.00
2
CUT
Q
r1170
CO: Frequency setpoint after RFG
-
3
-
-
Drive Features (P0004 = 12)
ParNr ParText
Default
Acc
WS
QC
P0005[1] Display
selection
21
2 CUT
N
P0006 Display
mode
2 3 CUT
N
P0007
Backlight delay time
0
3
CUT
N
P0011
Lock for user defined parameter
0
3
CUT
N
P0012
Key for user defined parameter
0
3
CUT
N
P0013[20]
User defined parameter
0
3
CUT
N
P1200 Flying
start
0 2 CUT
N
P1202[1] Motor-current:
Flying
start
100 3 CUT
N
P1203[1]
Search rate: Flying start
100
3
CUT
N
P1210 Automatic
restart
1 2 CUT
N
P1211
Number of restart attempts
3
3
CUT
N
P1215
Holding brake enable
0
2
T
N
P1216
Holding brake release delay
1.0
2
T
N
P1217
Holding time after ramp down
1.0
2
T
N
P1232[1]
DC braking current
100
2
CUT
N
P1233[1]
Duration of DC braking
0
2
CUT
N