2 command sources (p0700), 3 off and braking functions, 1 off1 – Siemens MICROMASTER 411 User Manual
Page 63
Issue 03/01
4 Using the MICROMASTER 411 / COMBIMASTER 411
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
63
4.2
Command Sources (P0700)
NOTICE
The ramp times and ramp-smoothing functions also affect how the motor starts
and stops. For details of these functions, please refer to parameters P1120, P1121,
P1130 – P1134 in the Parameter List.
Starting the motor
Default
Terminal 1 (DIN 1): (P0700=2)
Other Settings
see P0700 to P0704
Stopping the motor
There are several ways to stop the motor:
Default:
♦
OFF1 (4.3.1)
Terminal 1 (DIN 1): (P0700=2)
♦
OFF2 (4.3.2)
Off button on BOP/AOP. Pressing the Off button once
(two seconds) or twice (with default settings). This is not
possible without BOP/AOP
♦
OFF3 (4.3.3)
no standard setting
Other Settings
see P0700 to P0704
Reversing the motor
Default
Terminal 2 (DIN 2)
Other Settings
see P0700 to P0704
4.3
OFF and Braking Functions
4.3.1 OFF1
This command (produced by canceling the ON command) causes the inverter to
come to a standstill at the selected ramp-down rate.
Parameter to change ramp time see P1121
NOTICE
ON and the following OFF1 command must have the same source.
If the ON/OFF1 Command is set to more than one Digital input, only the last
set Digital Input is active e.g. DIN3 active.
OFF1 can be combined with DC braking or Compound braking.