3 Commissioning
Issue 03/01
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
50
6SE6400-5CA00-0BP0
3.3.4.1 Commissioning
with
the
Basic Operator Panel (BOP)
The Basic Operator Panel (BOP), which is available as an
optional accessory, provides the user with access to the
inverter parameters and enables you to customize the
settings of your COMBIMASTER 411 & MICROMASTER
411. The BOP is mounted in an Operator Panel Mounting
Kit and connected to the COMBIMASTER 411 &
MICROMASTER 411 via the serial interface (see Figure
3-9). The BOP can be used to configure several
COMBIMASTER 411 & MICROMASTER 411 Inverters.
The BOP features a five-digit, seven-segment display for
showing parameter numbers and values, alarm and fault messages and setpoints
and actual values. Parameter sets cannot be saved via the BOP.
Control functions for the inverter (ON/OFF,
,
, reverse) are not active in the
works settings. In order to specify this command via the BOP, P0700 = 1 must be
set.
If the BOP connection is removed during normal running the drives is stopped and
the motor coasts to standstill.
Table 3-5 shows the factory default settings for operation via the BOP.
Table 3-5
Default Settings for BOP Operation
Parameter Meaning
Default
Europe
(North
America)
P0100
Operating Mode Europe/US
50 Hz, kW (60 Hz, hp)
P0307
Power (rated motor)
kW (Hp)
P0310
Motor frequency rating
50 Hz (60 Hz)
P0311
Motor speed rating
1395 (1680) rpm [depending on variant]]
P1082
Maximum Motor Frequency
50 Hz (60 Hz)