3 Commissioning
Issue 03/01
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
58
6SE6400-5CA00-0BP0
3.4.3
Non - Default Modes of Operation
Non-default modes of operation require the use of either a Keypad (BOP or AOP)
or a Commissioning tool (Drive Monitor or Starter) in order to change from the
default parameter settings.
The BOP, Part Number: 6SE6400-0BP00-0AA0 is housed in an Operator Panel
Mounting Kit, Part Number 6SE6401-1DF00-0AA0 and connected via the Interface
Link Cable, Part Number 6SE6401-1BL00-0AA0 to the Inverter serial comms port.
This arrangement is shown in Figure 3-9.
Figure 3-9
Connect BOP/AOP with the MICROMASTER 411
Prerequisites
P0010 = 0 (in order to initiate the run command correctly).
P0700 = 1 (enables the start/stop button on the BOP).
P1000 = 1 (this enables the motor potentiometer setpoints).
1. Press the green Button
to start the motor.
2. Press the Button
while the motor is turning. Motor speed increases to
50 Hz.
3. When the inverter reaches 50 Hz, press the Button
. Motor speed and
display is decreased.
4. Change the direction of rotation with the
Button
.
5. The red button stops the motor
.