beautypg.com

Siemens MICROMASTER 411 User Manual

Page 51

background image

Issue 03/01

3 Commissioning

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

51

Buttons on the Basic Operator Panel

Panel/Button Function

Effects

Indicates

Status

The LCD displays the settings currently used by the inverter.

Start motor

Pressing the button starts the inverter. This button is disabled by
default. To enable this button set P0700 = 1.

Stop motor

OFF1 Pressing the button causes the motor to come to a standstill

at the selected ramp down rate. Disabled by default; to
enable set P0700 = 1.

OFF2 Pressing the button twice (or once long) causes the motor to

coast to a standstill. This function is always enabled.

Change

direction

Press this button to change the direction of rotation of the motor.
Reverse is indicated by a minus (-) sign or a flashing decimal point.
Disabled by default, to enable set P0700 = 1.

Jog motor

Pressing this button while the inverter has no output causes the
motor to start and run at the preset jog frequency. The motor stops
when the button is released. Pressing this button when the motor is
running has no effect.

Functions

This button can be used to view additional information.
Pressing and holding the button for 2 seconds from any parameter
during operation, shows the following:
1. DC link voltage (indicated by d – units V).
2. Output current. (A)
3. Output frequency (Hz)
4. Output voltage (indicated by o – units V).
5. The value selected in P0005 (If P0005 is set to show any of the

above (1 to 4) then this will not be shown again).

Additional presses will toggle around the above displays.
Jump Function
From any parameter (rXXXX or PXXXX) a short press of the Fn
button will immediately jump to r0000, you can then change another
parameter, if required. Upon returning to r0000, pressing the Fn
button will return you to your starting point.
Quit

In case of a fault or alarm the

button resets the fault or alarm

message on the operator panel display.

Access

parameters

Pressing this button allows access to the parameters.

Increase

value

Pressing this button increases the displayed value.

Decrease

value

Pressing this button decreases the displayed value.

Figure 3-5

Basic Operator Panel Controls