Figure 10-8 Response to 5 Hz step: T = 700 ms

The frequency step

f = 5 Hz / 50 Hz = 10 %

The feedback step

x = 0.64 V / 10 V = 6.4 %

P gain = (0.9)(T)(

f) / (L)(

x) = 9.84 = P2280

I time = 3L = 0.30 s = P2285

The PI controller should now be enabled (P2200 = 1).

Figure 10-9 Step Response in PI control with P2280 = 9.84 and P2285 = 0.30