beautypg.com

2 control circuit jumpers – Siemens MICROMASTER 411 User Manual

Page 47

background image

Issue 03/01

3 Commissioning

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

47

Behaviour of the Ramp Time Jumpers

In Table 3-2 the behaviour of the Ramp Time Jumpers are explained:

Table 3-2

Ramp Time Jumper Behaviour

Status before action(s)

Action(s)

Reaction(s) of the inverter

No jumper fitted
Ramp times have arbitrary setting

Power down

Fit jumper(s)

Power up

Inverter uses the ramp times defined by the current
jumper setting

At least one Jumper fitted
Ramp times have arbitrary setting

Power down

Power up

Inverter uses the ramp times defined by the current
jumper setting

At least one Jumper fitted
Ramp times have arbitrary setting

Power down

Remove jumper(s)

Power up

Inverter uses the ramp times that were used before
removing the jumper(s)


NOTE
The brake time is influenced by the setting for the ramp time (deceleration time).
The following relationship applies:


3.3.2

Control Circuit Jumpers

Control Jumpers (see Table 3-3) are provided for the following functions (fit jumper
to enable function). Jumpers can only be accessed when the cover is removed:

Pot = Run
Enables the control potentiometer as the Command Source (auto restart is
enabled).

24 V AIN
To change analogue input range from 0 –10 V to 0 – 24 V

DC Brake
To change Stop function from OFF1 to DC Brake.

Fan/Pump: M~n2
To change V/f curve from Linear to Quadratic curve.

60 Hz operation

To change motor default settings from 50 Hz to 60 Hz.

Braking time = P1121 (deceleration time) *

P0305 (nominal motor current)
r0207 (nominal inverter current)