beautypg.com

4 derating factors, 1 derating with temperature, 2 derating with altitude – Siemens MICROMASTER 411 User Manual

Page 135

background image

Issue 03/01

10 Engineering Information

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

135

10.4 Derating

Factors

10.4.1 Derating

with

Temperature

Operation of the inverter outside its recommended ambient operating temperature
would normally cause the inverter to trip with an overtemperature fault code. To
avoid such tripping, the inverter automatically reduces its switching frequency (e.g.
from 16 kHz to 8 kHz), thus reducing the temperature of the heatsink, enabling the
application to continue running trip free. Should the load or ambient temperature
then reduce, the inverter will first check to see if it is safe to increase the switching
frequency again and if considered safe will then do so.

80

60

40

0

20

100

-10

0

70

10 20

30

40

50

60

°C

%

Rat

ed Out

put

Current

Figure 10-16 Reduktionsfaktoren durch die Umgebungstemperatur

10.4.2 Derating

with

Altitude

Figure 10-17 shows the permissible rated input voltage and output current for
inverter installations from 500 m to 4000 m above sea level.

Input

v

ol

tage

Permissible rated input voltage as a
percentage of the nominal voltage

100

90

80

60

70

1000

2000

3000

4000

500

500

100

90

80

60

70

1000

2000

3000

4000

Permissible rated output current as a
percentage of the nominal current

Rat

ed out

put

c

urrent

Installation altitude in meters above sea level

Figure 10-17 Derating with Altitude