3 control cable connections – Siemens MICROMASTER 411 User Manual
Page 37
Issue 03/01
2 Installation
MICROMASTER 411 & COMBIMASTER 411 Operating Instructions
6SE6400-5CA00-0BP0
37
2.5.3
Control Cable Connections
1. Feed the control cables into the inverter via one of the gland holes at the I/O
module end of the terminal housing.
2. Run the control cable underneath the I/O board toward the control terminals.
3. Connect the control wires in accordance with the terminal information given in
Figure 2-11.
4. Use screened cable for all control wiring.
8 9
1 2 3 4 5 6 7
Terminal Inputs Parameter
Default
operation
1
DIN 1
P0701 = ‘1’
ON/OFF1
2
DIN 2
P0702 = ‘12’
Reverse
3
DIN 3
P0703 = ‘9’
Fault Acknowledge
6/7
AIN (-/+)
P0756 = 0
0 – 10 V Analogue Input
Option: DIN 4
P0704
≠
0
8/9
Output Relay
P0731 = ’52.3’
Fault identification
Figure 2-11 Control Terminals
NOTE
If a PTC resistor is fitted, this
should be connected between 4
(+24 V) and 3 (DIN 3).