beautypg.com

3 control cable connections – Siemens MICROMASTER 411 User Manual

Page 37

background image

Issue 03/01

2 Installation

MICROMASTER 411 & COMBIMASTER 411 Operating Instructions

6SE6400-5CA00-0BP0

37

2.5.3

Control Cable Connections

1. Feed the control cables into the inverter via one of the gland holes at the I/O

module end of the terminal housing.

2. Run the control cable underneath the I/O board toward the control terminals.
3. Connect the control wires in accordance with the terminal information given in

Figure 2-11.

4. Use screened cable for all control wiring.

8 9

1 2 3 4 5 6 7

Terminal Inputs Parameter

Default

operation

1

DIN 1

P0701 = ‘1’

ON/OFF1

2

DIN 2

P0702 = ‘12’

Reverse

3

DIN 3

P0703 = ‘9’

Fault Acknowledge

6/7

AIN (-/+)

P0756 = 0

0 – 10 V Analogue Input

Option: DIN 4

P0704

0

8/9

Output Relay

P0731 = ’52.3’

Fault identification

Figure 2-11 Control Terminals

NOTE

If a PTC resistor is fitted, this
should be connected between 4
(+24 V) and 3 (DIN 3).