Sanyo DHX4852 User Manual
Page 66
3-18
Control of W-2WAY ECO-i SYSTEM
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
2. Wireless Remote Controller
2-14. Wiring the Separate Receiver Unit
*
Use wires that are AWG#20 to AWG#14 in diameter.
*
The wiring length must not exceed 1320 ft.
Connection diagram
Wire of
receiver
unit (field
supply)
Power wire from
receiver unit
Separate
receiver unit
Connector
Indoor unit
remote controller
terminal board
1
2
1
2
WHT
BLK
Wire of receiver unit
(field supply)
Power wire from
receiver unit
1. Strip the insulation to approximately 35/64”
from the ends of the wires to be connected.
2. Twist together the 2 wires and create a
crimp connection at the wire joint.
3. If a special crimping tool is not used, or if
the connection is soldered, insulate the
wires using insulation tape.
Provided
wire joint
(WHT 2)
Wire joint
CE-1 (provided)
Remote controller cord (optional)
Separate
receiver unit
Indoor unit
remote controller
terminal board
1
2
WHT
BLK
1
2
Connection diagram
Use the remote controller cord (optional) for wiring the
separate receiver unit.
1. For the methods used to install the remote controller cord,
refer to “For flush mounting into a wall, install the sepa-
rate receiver unit in a metal switch box (field supply) that
has been recessed into the wall in advance” on P. 3-16.
2. When using the remote controller cord (optional), refer to
the instruction manual that came with the cord.
Check the terminal number on the indoor unit before wir-
ing the remote controller and be sure not to wire incor-
rectly. (The unit will be damaged if high voltage, such as
200 VAC, is applied to it.)
TD831138-02_W-2WAY.indb 18
2007/07/26 14:31:22