beautypg.com

System design – Sanyo DHX4852 User Manual

Page 28

background image

2-18

Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Indoor unit changes

The indoor unit in room 4, where the corrected indoor unit capacity is less than the maximum load, is increased by one rank.

Outdoor unit

Room 1
(indoor unit 1)

Room 2
(indoor unit 2)

Room 3
(indoor unit 3)

Room 4
(indoor unit 4)

Selected model

Type 14053+09053

Type 4852

Type 4852

Type 3652

Type 2452

Maximum load
(cooling/heating) (BTU/h)

40,000 / 46,000

40,000 / 46,000

30,000 / 35,000

18,000 / 23,000

Rated capacity
(cooling/heating) (BTU/h)

249,100 / 278,100

47,800 / 54,600

47,800 / 54,600

36,000 / 39,000

25,000 / 27,000

(5) Corrected capacity

(cooling/heating) (BTU/h)

208,100 / 201,900

47,400 / 54,600

46,300 / 54,600

34,000 / 38,900

23,000 / 26,400

(7) Actual capacity

(cooling/heating) (BTU/h)

47,400 / 54,600

46,300 / 54,600

34,000 / 38,900

23,000 / 26,400

Total corrected capacity of all indoor units (cooling/heating) = 150,700/174,500
Ruc = 150,700/208,100 = 0.724 < 1 Ruh = 174,500/201,900 = 0.864 < 1

For both cooling and heating in all rooms, actual capacity is now greater than or equal to the maximum load. Selection is
completed.

(2) Calculate the final selection results according to the capacity calculation procedure.

[From calculation of the correction coefficient to calculation of actual capacity]

(Cooling/heating)

Outdoor unit

Room 1
(indoor unit 1)

Room 2
(indoor unit 2)

Room 3
(indoor unit 3)

Room 4
(indoor unit 4)

Rated capacity (BTU/h)

249,100 / 278,100

47,800 / 54,600

47,800 / 54,600

36,000 / 39,000

25,000 / 27,000

Correction coefficient

(1) Model

1.00 / 1.00

(2) Temp. condition

1.020 / 0.937

0.921 / 0.780

0.921 / 0.980

0.921 / 0.980

0.921 / 0.980

(3) Tubing length,

elevation difference

0.819 / 0.871

1.077 / 1.052

1.052 / 1.035

1.026 / 1.017

1.00 / 1.00

(4) Frosting/defrosting

0.89

Result of (2) × (3)

0.992 / 1.031

0.969 / 1.014

0.945 / 0.997

0.921 / 0.980

Correction coefficient
applied to indoor unit *1

0.99 / 1.03

0.97 / 1.01

0.95 / 1.00

0.92 / 0.98

(5) Corrected capacity (BTU/h) *2

208,100 / 201,900

47,400 / 54,600

46,300 / 54,600

34,000 / 38,900

23,000 / 26,400

(6) Correction coefficient

for corrected capacity ratio

1.00 / 1.00

(7) Actual capacity (BTU/h)

47,400 / 54,600

46,300 / 54,600

34,000 / 38,900

23,000 / 26,400

*1: This varies depending on the values of (2) and (2) × (Distribution ratio in (3)).
*2: Corrected outdoor unit capacity = Rated outdoor unit capacity Ч (1) Ч (2) Ч (3) Ч (4)

The actual capacity is calculated as shown below.

Cooling: Ruc = (47,400 + 46,300 + 34,000 + 23,000) / 208,100 = 0.724 < 1
Therefore,
Actual cooling capacity of each indoor unit = Corrected cooling capacity of each indoor unit
(In other words, the correction coefficient (6) for the corrected capacity ratio is 1.)
Heating: Ruh = (54,600 + 54,600 + 38,900 + 26,400) / 201,900 = 0.864 < 1
Therefore,
Actual heating capacity of each indoor unit = Corrected heating capacity of each indoor unit Ч (0.1 Ч Ruh + 0.9) / Ruh
(In other words, the correction coefficient (6) for the corrected capacity ratio is (0.1 × Ruh + 0.9) / Ruh.)

2. System Design

TD831138-02_W-2WAY.indb 18

2007/07/26 14:30:42

This manual is related to the following products: