Outdoor unit – Sanyo DHX4852 User Manual
Page 118
4-4
W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1. Outdoor Unit
Unit Specifications (3)
MODEL NAME
W-2WAY ECO-i Capacity Control Outdoor Unit <20 horsepower>
GENERAL MODEL No.
WCHDX20053
COMPONENT OUTDOOR UNIT
CHDX09053
CHDX09053
POWER SOURCE
208-230V/3ø/60Hz
208-230V/3ø/60Hz
PERFORMANCE
Cooling capacity
BTU / h (kW)
191,100 (56.0)
Heating capacity
BTU / h (kW)
215,000 (63.0)
UNIT DIMENSIONS
Height
in. (mm)
74-9/32 (1887)
Width
in. (mm)
74 (1880)
Depth
in. (mm)
Ceiling dimension : 35-1/32 ~ +2-3/8
(890 ~ +60)
Net weight
lbs. (kg)
650 (295)
650 (295)
Color (Munsell code)
Silky shade (1Y 8.5 / 0.5)
ELECTRICAL RATINGS
Voltage rating
V
208
230
Cooling
Running amperes
A
66.2
61.4
Power input
kW
15.8
15.8
Power factor
%
66
65
Heating
Running amperes
A
66.2
61.4
Power input
kW
15.5
15.5
Power factor
%
65
63
Starting amperes
A
164
160
COMPRESSOR
Type - Q'ty
Hermetic type x 2
Hermetic type x 2
Motor output
kW
3 + 3.75
3 + 3.75
Refrigeration oil
Type
FV68S (Ether oil)
Charge amount
gal
1.29
1.29
Crankcase heater
W
25 + 32
25 + 32
Capacity control
%
–
Refrigerant amount at shipment
lbs. (kg)
R410A - 26.5 (12.0)
R410A - 26.5 (12.0)
Refrigerant control
Electronic expansion valve
Defrost method
Reverse-cycle defrost, outdoor unit cycle defrost
Heat exchanger
Aluminum plate fin / Copper tube
FAN DEVICE
Type - Q'ty
Propeller fan x 1
Propeller fan x 1
Air circulation
CFM
5,650
5,650
External static pressure
in.WG
0
0
Motor output (No. of poles)
kW
0.7/8P
0.7/8P
Protective devices
High pressure switch, overcurrent (CT method)
TUBING
Refrigerant tubing
Gas tube
in. (mm)
ш7/8 (ш22.22) (Brazing)
Liquid tube
in. (mm)
ш3/8 (ш9.52) (Flare nut)
Balance tube
in. (mm)
ш1/4 (ш6.35) (Flare nut)
Drain port
–
External air temperature operation range
°F
Cooling: 14 ~ 109 °F (DB)
Heating: -4 ~ 59 (WB)
Operation sound (Hi)
dB-A
58.0 (Quiet mode: 55.0)
Primary accessories
Connection tubing
ш7/8 (ш22.22)
Connection tubing
ш7/8 (ш22.22)
* Performance, electrical characteristics values and operating sound are based on JIS B8616 package A/C.
(Colling : Indoor intake air temperature 80°F DB / 67°F WB. Outdoor intake air temperature 95°F DB.)
(Heating : Indoor intake air temperature 70°F DB. Outdoor intake air temperature 47°F DB / 43°F WB.)
TD831138-02_W-2WAY.indb 4
2007/07/26 14:32:08