Model selecting and capacity calculator – Sanyo DHX4852 User Manual
Page 25

1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
2-15
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
El
ev
ation dif
ference (ft
)
Base capacity
change rate
*1
92 90
88
86 84 82 80
78
76
94
96
98
100
%
0
33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
0
33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
164
131
98
66
33
0
–33
–66
–98
–131
Equivalent length (ft)
*1 Sample calculations
(System: 20 HP, 164ft equivalent length, 49ft elevation
difference
The cooling capacity and heating capacity for this system are
found as shown below.)
●
Cooling operation
From the table, the correction coefficient for that horsepower
level is found to be 1.00.
From the graph, the base capacity change rate is found to be
92.0%.
92.0%
×
1.00 = 92.0%
Capacity change rate is 92.0%.
(56.0kW
×
92.0% = 51.5kW)
92.0% = 175,800 BTU/h
Cooling capacity is
175,800 BTU/h (51.5 kW)
●
Heating operation
From the table, the correction coefficient for that horsepower
level is found to be 1.00.
From the graph, the base capacity change rate is found to be
97.2%.
97.2%
×
1.00 = 97.2%
Because the calculation result exceeds 97.2%, the capacity
change rate is 97.2%.
(63.0kW
×
97.2% = 61.2kW)
Heating capacity is
209,000 BTU/h (61.2 kW)
Cooling
Heating
Item
Model (SPW-)
Cooling
capacity
(kW)
Power
consumption
(kW)
Heating
capacity
(kW)
Power
consumption
(kW)
<50Hz models>
22.4
28.0
33.5
40.0
45.0
5.99
7.90
9.58
11.6
13.3
25.0
31.5
37.5
45.0
50.0
6.17
7.15
9.60
11.5
13.2
Equivalent length (ft)
Base capacity
change rate
164
131
98
66
33
0
–33
–66
–98
–131
0
33 66 98 131 164 197 230 262 295 328 361 394 427 459 492
El
ev
ation dif
ference (ft
)
191,100 BTU/h
×
97.2% = 209,000 BTU/h
215,000 BTU/h
×
1-8. Capacity Correction Graph According to Tubing Length and Elevation Difference
Capacity change characteristics
The positive side for the elevation difference indicates that
the outdoor unit is installed at a higher position than the
indoor units. The negative side indicates the opposite.
NOTE
1. Model Selecting and Capacity Calculator
Rated performance values
Item
Cooling
Heating
Type
Cooling capacity
BTU/h(kW)
Power consumption
BTU/h(kW)
Heating capacity
BTU/h(kW)
Power consumption
BTU/h(kW)
90
95,500(28.0)
27,000(7.90)
107,500(31.5)
26,500(7.75)
140
153,600(45.0)
45,400(13.3)
170,600(50.0)
45,000(13.2)
TD831138-02_W-2WAY.indb 15
2007/07/26 14:30:40