Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

Check of limit density

Pay special attention to any location,
such as a basement, etc., where leaking
refrigerant can accumulate, since
refrigerant gas is heavier than air.

WARNING

CAUTION

1. Model Selecting and Capacity Calculator

Additional refrigerant charge amount

Additional refrigerant charge amount is calculated from the liquid tubing total length as follows.

Table 2-12 Amount of Refrigerant Charge Per Meter, According to Liquid Tubing Size

Liquid tubing size

Amount of refrigerant

(in. (mm))

charge (oz/ft.)

ш1/4" (ш6.35)

0.279

ш3/8" (ш9.52)

0.602

ш1/2" (ш12.7)

1.38

ш5/8" (ш15.88)

1.99

ш3/4" (ш19.05)

2.78

ш7/8" (ш22.22)

3.93

Required amount of charge = (Amount of refrigerant charge per
meter of each size of liquid tube × its tube length) + (...) + (...)

* Always charge accurately using a scale for weighing.

WARNING

CAUTION

Always check the gas density
limit for the room in which the
unit is installed.

1-5. Check of Limit Density

When installing an air conditioner in a room, it is necessary to
ensure that even if the refrigerant gas accidentally leaks out, its
density does not exceed the limit level for that room.
If the density could exceed the limit level, it is necessary to provide
an opening between the unit and the adjacent room, or to install
mechanical ventilation which is interlocked with a leak detector.

(Total refrigerant charged amount: oz)

(Min. indoor volume where the indoor unit is installed: ft.

3

)

<

Limit density 0.3 (oz/ft.

3

)

The limit density of refrigerant R410A which is used in this unit is
0.3 oz/ft.

3

(ISO 5149).

The shipped outdoor unit comes charged with the amount of refrig-
erant fixed for each type, so add it to the amount that is charged in
the field. (For the refrigerant charge amount at shipment, refer to the
unit’s nameplate.)

Minimum indoor volume & floor area as against the amount
of refrigerant is roughly as given in the following table.

0

0

57

114

170

227

284

341

398

454

511

568

625

682

738

795

852

909

966

1022

1079

1136

0

500

1000

1500

2000

2500

3000

3500

4000

4500

5000

5500

6000

6500

7000

7500

8000

8500

9000

9500

10000

1000

500

1500 2000 2500 3000

Total amount of refrigerant

Min.

indoor v

olume

Min.

indoor floor area

(when the ceilin

g is 8.8 ft.

hi

gh)

ft.

3

ft.

2

oz

Range above
the density limit of
0.3 oz/ft.

3

(countermeasures
needed)

Range below
the density limit of
0.3 oz/ft.

3

(countermeasures
not needed)