beautypg.com

Model selecting and capacity calculator – Sanyo DHX4852 User Manual

Page 14

background image

2-4

Design of W-2WAY ECO-i SYSTEM Unit Specifications

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1

2

3

4

5

6

7

8

1. Model Selecting and Capacity Calculator

1-3. Tubing Length

R410A distribution joint
APR-CHP680BA (for outdoor unit)
APR-CHP680BA (for outdoor unit)
APR-CHP680BA (for outdoor unit)
APR-CHP680BA (for outdoor unit)
APR-P1350BA (for indoor unit)

Explanation of symbols

Distribution joint
(APR: purchased separately)

Solidly welded shut
(pinch weld)

Balance tubing
( 1/4")

Main distribution tubes LC – LG are selected according to the capacity after the distribution joint.

Sizes of indoor unit connection tubing 1 – 40 are determined by the connection tubing sizes on the indoor units.

Main tubing length LM = LA + LB … 262 ft

1.
2.
3. The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to the tube ends.
4.

Ball valve (field supply)

T-joint (field supply)

Note: Do not use commercially available T-joints for the liquid tubing and parts.

* Be sure to use special R410A distribution joints (APR: purchased separately) for outdoor unit connections and tubing branches.

Table 2-1 Ranges that Apply to Refrigerant Tubing Lengths and to Differences in Installation Heights

Select the installation location so that the length and size of refrigerant tubing are within the allowable range shown in the figure below.

Item

Mark

Contents

Length (ft.)

L1

Max. tubing length

Actual length

492

Equivalent length

574

L (L2 – L4)

Difference between max. length and min.
length from the No.1 distribution joint

131

LM

Max. length of main tubing (at max. diameter)

262

1, 2... 40

Max. length of each distribution tube

98

L1+ 1+ 2... 39+
A+LE+LF+LG

Total max. tubing length including length of
each distribution tube (only liquid tubing)

984

L5

L3

Distance between outdoor units

32

H1

When outdoor unit is installed higher than indoor unit

164

When outdoor unit is installed lower than indoor unit

131

H2

Max. difference between indoor units

49

H3

Max. difference between outdoor units

13

L = Length, H=Height

Allowable tubing
length

Allowable elevation
difference

*3

6.6

Allowable length of
joint tubing

T-joint tubing (field-supply); Max. tubing length between
the first T-joint and solidly welded-shut end point

1: The outdoor connection main tubing ( B portion) is determined by the total capacity of the outdoor units that are connected to

the tube ends.
2: If the longest tubing length (L1) exceeds 295 ft. (equivalent length), increase the sizes of the main tubes (LM) by 1 rank for gas

tubes and liquid tubes. (Use a field supply reducer.) (Select the tube size from the table of main tube sizes (Table 2-5) on the

following page (LA table), and from the table of refrigerant tubing sizes (Table 2-10) on the second following page.)
3: If the longest main tube length (LM) exceeds 164 ft., increase the main tube size at the portion before 164 ft. by 1 rank for the

gas tubes. (Use a field supply reducer.)

(For the portion that exceeds 164 ft., set based on the main tube sizes (LA) listed in the table on the following page.)
4: If the size of the existing tubing is already larger than the standard tubing size, it is not necessary to further increase the size.

* If the existing tubing is used, and the amount of on-site additional refrigerant charge exceeds the value listed below, then

change the size of the tubing to reduce the amount of refrigerant.

Max. additional charge for 1 outdoor unit: 62 lbs
Max. additional charge for 2 outdoor units: 111lbs

NOTE

L5

LA

LE

LM

LB

LC

L2

L4

LF

LD

L3

LG

H2

H3

H1

L1

2

3

1

5

4

A

B

38

39

40

For

extension

For

extension

Max. 1.3ft

Max. 1.3ft

TD831138-02_W-2WAY.indb 4

2007/07/26 14:30:27

This manual is related to the following products: