2-7
Design of W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1. Model Selecting and Capacity Calculator
Liquid tubing size
Amount of refrigerant
(in. (mm))
charge (oz/ft.)
ш1/4" (ш6.35)
0.279
ш3/8" (ш9.52)
0.602
ш1/2" (ш12.7)
1.38
ш5/8" (ш15.88)
1.99
ш3/4" (ш19.05)
2.78
ш7/8" (ш22.22)
3.93
Table 2-7 Amount of Refrigerant Charge
ш7/8"
(ш22.22)
ш3/8" (ш9.52)
ш1/4" (ш6.35)
95,500
(28.0)
153,600
(45.0)
ш1-1/8"
(ш28.58)
Flare connection
Brazing connection
ш1/2" (ш12.7)
Flare connection
(
A
–
B
)
Balance tubing
Liquid tubing
Gas tubing
BTU/h
(kW)
Table 2-8 Outdoor Unit Tubing Connection Size
Table 2-9 Indoor Unit Tubing Connection Size
Balance tube
Liquid tube
Gas tube
ш5/8" (ш15.88)
ш3/8" (ш9.52)
ш1/4" (ш6.35)
ш1/2" (ш12.7)
Gas tubing
Liquid tubing
Indoor unit type
7
9
12
18
24
36
48
Note: Use C1220T-1/2H material for tubing over ш3/4" (ш22.22).
Unit: in. (mm)
Unit: in. (mm)
Table 2-10 Refrigerant tubing (Existing tubing can be used.)
Tubing size (in. (mm))
Material O
Material 1/2H • H
ш1/4" (ш6.35)
t1/32" (0.8)
ш7/8" (ш22.22)
t5/128" (1.0)
ш3/8" (ш9.52)
t1/32" (0.8)
ш1" (ш25.40)
t5/128" (1.0)
ш1/2" (ш12.7)
t1/32" (0.8)
ш1-1/8" (ш28.58)
t5/128" (1.0)
ш5/8" (ш15.88)
t5/128" (1.0)
ш1-1/4" (ш31.75)
t3/64" (1.1)
ш3/4" (ш19.05)
over t5/128" (1.0)
ш1-3/8" (ш34.93)
over t3/64" (1.15)
* When bending the tubes, use a bending
radius that is at least 4 times the outer
diameter of the tubes.
In addition, take sufficient care to avoid
crushing or damaging the tubes when
bending them.