Test run – Sanyo DHX4852 User Manual
Page 199
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
5-7
Test Run
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
1-1
1-2
2-1
2-2
2-9
1-3
1-13
2
9
2
1
ON
3
ON
1
2
3
ON
1
2 3
3
2
1
ON
ON
1 2 3
ON
1
2
2
ON
1
3
1
1
ON
3
2
ON
1 2
2
ON
1
3
3
2
1
ON
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
ON
OFF
OFF
ON
Automatic address setting in Heating mode
Automatic address setting in Cooling mode
Leave the socket that
is used to short-circuit
the terminal plug.
(CN003)
To other system
link wiring
· Indoor and outdoor unit power can be turned ON for each system separately.
Case 3A
Case 2
Case 3B
Make settings as appropriate for the cases listed below.
(Refer to the instructions on the following pages.)
Move the socket to
the “OPEN” side
(CN003).
(S006)
(S007)
(S005)
(S004)
(S003)
(S002)
No. 1 (main outdoor unit) settings
No. 2 (sub unit)
Unit
No. 2
(Sub)
Unit
No. 3
(Sub)
Unit
No. 1
(Main)
Outdoor unit
system 1
Unit
No. 2
(Sub)
Unit
No. 1
(Main)
Outdoor unit
Indoor unit
Remote
controller
Indoor unit
Remote
controller
Outdoor main/sub
control wiring
Outdoor main/sub control wiring
Inter-unit control wiring
Inter-unit control wiring
Remote controller
communication wiring
Remote controller
cross-over wiring
(S007)
No. 2 (sub unit) settings
(S007)
No. 3 (sub unit)
(S007)
(S006)
(S007)
(S005)
(S004)
(S003)
(S002)
No. 1 (main unit) settings
System address
(system 1 setting)
System address
(system 2 setting)
No. of indoor units
(13 units setting)
No. of indoor units (9
No. of
outdoor
units (2 units
setting)
No. of
outdoor units
(3 units
setting)
Unit
number
setting
(unit No. 1)
Unit
number
setting
(unit No. 2)
Unit
number
setting
(unit No. 3)
Unit
number
setting
(unit No. 2)
Unit
number
setting
(unit No. 1)
system 2
· Indoor and outdoor unit power cannot be turned ON for each system separately.
No. 2
Refrigerant
circuit
Fig. 5-6
5. TEST RUN
Basic wiring diagram: Example (2)
• If link wiring is used
* When multiple outdoor main units exist, remove the socket that is
used to short-circuit the terminal plug (CN003) from all outdoor
main unit PCBs except for one unit.
Alternatively, move the sockets to the “OPEN” side.
TD831138-02_W-2WAY.indb 7
2007/07/26 14:33:19