1-way air discharge semi-concealed type (a type) – Sanyo DHX4852 User Manual
Page 140
4-26
W-2WAY ECO-i SYSTEM Unit Specifications
1
2
3
4
5
6
7
8
1
2
3
4
5
6
7
8
3. 1-Way Air Discharge Semi-concealed Type (A Type)
Unit specifications (C)
MODEL No.
Indoor Unit
AHX1252
POWER SOURCE
208 - 230 V / 1ø / 60 Hz
PERFORMANCE
Cooling
Heating
Capacity
BTU / h
12,000
14,000
kW
3.6
4.2
Air circulation (Hi / Me / Lo)
CFM
320 / 280 / 250
Moisture removal (High)
Pints / h
4.02
–
ELECTRICAL RATINGS
Voltage rating
V
208
230
208
230
Available voltage range
V
187 - 253
187 - 253
Running amperes
A
0.32
0.31
0.34
0.32
Power input
W
52
55
50
52
Power factor
%
78
77
71
71
Max. starting amperes
A
1
1
1
1
FEATURES
Controls
Microprocessor
Fan speeds
3 and Automatic control
Airflow direction
Automatic (Remote control)
Air filter
Washable, easy access, long life
Refrigerant control
Electronic expansion valve
Operation sound (Hi / Me / Lo)
dB-A
33 / 31 / 29
Refrigerant tubing connections
Flare type
Refrigerant tube di-
ameter
Liquid tube
in. (mm)
1 / 4 (6.35)
Gas tube
in. (mm)
1 / 2 (12.7)
Drain connection
25 A, OD 1-1/4"
Drain pump
Max. head 2.1 ft. above drain connection
Panel
Optional (PNR-AH1252)
Remote controller
Optional (RCS-TM80BG, RCS-TRP80AAB.WL)
Refrigerant tubing kit / Accessories
Optional / –
Color (Approximate value)
Munsell 2.5GY 9.0 / 0.5, RAL 9001-GL (resemblant color)
DIMENSIONS & WEIGHT
Indoor unit (including panel)
Package
Body
Panel
Unit dimensions
Height
in. (mm)
13 (330)
14-3 / 16 (360) 4-13 / 32 (112)
Width
in. (mm)
29-29 / 32 (760)
31-3 / 32 (790) 31-1 / 2 (800)
Depth
in. (mm)
24-3 / 8 (620)
23-15 / 32 (596) 27-9 / 16 (700)
Net weight
lbs. (kg)
43 (19.5)
–
–
Shipping weight
lbs. (kg)
–
64 (29)
9 (4.0)
Shipping volume
ft
3
(m
3
)
–
6.0 (0.170)
2.2 (0.062)
Rated conditions
Colling : Indoor air temperature 80°F DB / 67°F WB ; Outdoor air temperature 95°F DB
Heating : Indoor air temperature 70°F DB ; Outdoor air temperature 47°F DB / 43°F WB
TD831138-02_W-2WAY.indb 26
2007/07/26 14:32:49