Remote Control Functions
4. System Controller (SHA-KC64UG)
2
(c) Automatic zone registration using the system controller
(SHA-KC64UG)
(1) Press the
and
buttons at the same time for more than 4
seconds.
and CODE No. C1 will flash.
(2) Select CODE. No. C2 by pressing
and
(
) button
and press the
button.
C2 changes from flashing to ON state and automatic zone
registration will start.
(3) Any registered GROUP Nos. will be erased.
(4) Central address will be assigned from smallest indoor unit address
to larger ones in numerical order automatically.
On finishing automatic zone registration,
changes from flashing
to OFF.
(5) If an error occurs, “CHECK” starts flashing and zone
registration finishes at this time. Press the
button to start over.
(6) Finally, complete automatic zone registration mode by pressing the
button.
flashes for a few minutes, then turns OFF.
How to check for overlapping of central address Nos.
(1) Press the
and
buttons at the same time for more than 4
seconds.
and CODE No. C1 will flash.
(2) Select CODE. No. C3 by pressing
,
(
) button and
press the
button.
C3 changes from flashing to ON state and
will flash. Then
auto overlap checking will start.
(3) If C3 changes from ON to flashing and
stops flashing and
disappears, there is no overlapping.
Then finally, complete the auto overlap checking mode by pressing
the
button.
(4) If some of GROUP No., ZONE No. and UNIT No. flash, you should
try the zone registration again.
Select CODE No. C1 by pressing
,
(
) button and
press the
button.
Select the flashing GROUP No. with ZONE and GROUP button.
Then press the
button and reselect the ZONE, GROUP and
UNIT No.
Then finally, complete the auto overlap checking mode by
pressing the
button.