Section 3

WattMaster WHP

3-30

Programming

Setpoint Screen #9

Setpoint Screen #10

Setpoint Screen #11

WHP Loop Setpoints

Lead/Lag Changeover

Switch After xxx Hrs

The two pumps will switch after this programmed amount of
time so that each pump accumulates roughly the same
number of run time hours. If a pump is currently running and
this time period is exceeded, the changeover will occur as
soon as pump run time exceeds the setpoint. The current
pump will shut off and the standby pump will start at the
same time.

Minimum

Default

Maximum

Changeover

1 Hour

40 Hours

240 Hours

WHP Loop Setpoints

Water Loop Proof Of

Flow Pr. SP: xxx PSI

If you attached a Pressure Sensor for proof of flow instead of a
differential pressure contact closure for proof of flow, the
controlling pressure is programmed on this screen. This
Setpoint represents the amount of pressure that you set to prove
water flow exists in the system. Otherwise, this screen will not
appear.

Minimum

Default

Maximum

Flow PR. SP

0

5 PSI

50 PSI

If you configured the system for Variable Speed Pumping with
a Pressure Sensor for proof of flow, the controlling pressure,
deadband and control adjust time period are programmed on
this screen. Otherwise, this screen will not appear.

WHP Loop Setpoints

Pressure SP: xxx PSI

SP Deadband: xx PSI

Adjust Time: x.x Sec

Minimum

Default

Maximum

Pressure SP

1 PSI

40 PSI

50 PSI

SP Deadband

1 PSI

2 PSI

50 PSI

Adjust Time

0.1 Seconds

1.0 Seconds

25 Seconds