beautypg.com

3 checking the commlink ii driver – Heat Controller Water Source Heat Pump User Manual

Page 108

background image

WattMaster WHP

Section 4

4-26

Start-Up and Troubleshooting

5.3.3

Checking the CommLink II Driver

Diagram

Overview

This test checks for proper Network loop voltages coming from the CommLink II.

Tip: The Loop LED (located on the front panel) should “flicker” when the CommLink II is

attempting to communicate. The Loop LED will flicker more noticeably for a few
seconds when first powered up. If the LED does not flicker, the unit is not function-
ing.

Proper loop voltages are essential for reliable communications. It is normal to see fluctua-
tions at this point on the CommLink II. The average value should be close to the acceptable
range described below. Values will vary upon initial powerup for about 10-15 seconds as
the unit attempts to communicate.

Measurements

Local Loop

Acceptable Range

T – G
(SHLD)

2.4 - 2.5 Volts DC

R – G
(SHLD)

2.5 - 2.7 Volts DC

Action

Condition

Action

If voltages are too high or too low on either
side

1. The CommLink II has a damaged comm

driver chip. Replace the driver chip.
See instructions in section 1.3.11 for
“Comm Driver Chip Replacement”.

2. The CommLink II is defective.