Section 2

WattMaster WHP

2-16

Installation and Wiring

The WHP Controller requires the following electrical connections:
18 Gauge minimum unless otherwise noted.

-24VAC Supply Voltage........................................................................... 2 Conductors
-Communications Loop ...................................... 2 Conductor twisted pair with shield

(WattMaster Cable, Belden #82760 or equivalent)

-Discharge Air Temperature Sensor .................................. (24 ga. Min.) 2 Conductors
-Room Air Temperature Sensor...........(24 ga. Min.) 2 Conductors for standard sensor

3 Conductors for sensors with setpoint adjustment

-Outside Air Temperature Sensor ....................................... (24 ga. Min.) 2 Conductors
-WHP Unit Control Wiring ......................................................... (24 ga.Min.) 24 VAC

Fan- ON/OFF

Rev Valve-ON/OFF

Compressor-ON/OFF

Heat Pump Reset

Aux. Heating or Cooling

Tip: After making all electrical connections it is advised to unplug all terminal blocks

on the WHP Controller until you are ready to begin the checkout procedure. This
may help to prevent damage if wiring errors occur elsewhere in the system
during installation or start-up.