M_me_nb, M_me_nc – ProSoft Technology 5201-DFNT-104S User Manual
Page 80

104S v2 ♦ ProLinx Gateway
IEC-60870-5-104 (104S) Protocol Implementation
(Firmware v2.xx)
Protocol Manual
Page 80 of 157
ProSoft Technology, Inc.
March 19, 2010
M_ME_NB
Monitored Measured Normalized Point
Associated Parameter Point
500 2500
501 2501
502 2502
503 2503
... ...
509 2509
In order to send a change of deadband for M_ME_NB Point 500, the client would
send a command type 110 to point 2500.
M_ME_NC
Monitored Measured Normalized Point
Associated Parameter Point
600 2600
601 2601
602 2602
603 2603
... ...
609 2609
In order to send a change of deadband for M_ME_NC Point 600, the client would
send a command type 110 to point 2600.