Event scan delay, Scan events, Time type – ProSoft Technology 5201-DFNT-104S User Manual
Page 23

Configure the Gateway
104S v2 ♦ ProLinx Gateway
Protocol Manual
(Firmware v2.xx)
ProSoft Technology, Inc.
Page 23 of 157
Event Scan Delay
1 to 65535, or 0 to disable
If set to 0, the feature will be disabled and the gateway will not generate any
events. If set from 1 to 65535, the parameter represents the number of
milliseconds between event scanning. This parameter defines how often the
program will scan for new events in the databases.
Scan Events
0 = N
O
S
CANNING
or 1 = S
CAN FOR
E
VENTS
Separate parameters exist for multiple point types. Defines whether events of this
point type will be generated by the gateway. If "No Scanning", then events will
not be generated. If "Scan for events", events will be scanned and generated on
change.
Time Type
0 = N
ONE
, 1 = CP24, or 2 = CP56
March 19, 2010