3.4.1 Control Data Transfer
The control communication typically occurs when the client sends a command
request to update the gateway’s command points. The data types addressing are
described in the following table.
Data Type
Data Size
Addressing Type
C_SC_NA 1
bit
Bit
C_DC_NA 2
bits
Bit
C_RC_NA 1
byte
Byte
C_SE_NA 1
word
Word
C_SE_NB 1
word
Word
C_SE_NC 2
words
Word
Some of the command points may be configured to be selected before executed.
Refer to the following parameter to configure the select/operate timeout period.
After the gateway receives the SELECT operation it will wait for this period of
time for the EXECUTE operation. If the gateway does not receive an EXECUTE
operation within this period of time it will require another SELECT operation
before the EXECUTE operation.