3.5.3 TESTFR Requests
Connections that are unused (but opened) may be periodically tested in both
directions by sending test messages (TESTFR=act) which are confirmed by the
receiving station sending TESTFR=con messages. The 104S v2 gateway can be
configured to periodically send this message using the following parameter:
In the example above, the gateway would send a TESTFR.ACT message 30
seconds after receiving the last message: