3.4.2 Command Points Addressing
Command points must be configured in a database area that is updated in the
gateway memory database. You must associate each point to a database
address in the 104S v2 gateway. The interpretation of the DB address parameter
in the configuration tables depends on the point type configured and the type of
addressing associated with that point type.
Data Type
Data Size
Addressing Type
C_SC_NA 1
bit
Bit
C_DC_NA 2
bits
Bit
C_RC_NA 1
byte
Byte
C_BO_NA 2
words
Double-word
C_SE_NA 1
word
Word
C_SE_NB 1
word
Word
C_SE_NC 2
words
Double-word
C_SC_NA and C_DC_NA
The single-point command and dual-point command points use one bit with bit-
addressing. For example, if you configure the following points:
These points would be used as follows:
Inf. Object Address
Module Database Address
100
Bit 0 of word 100
101
Bit 1 of word 100
102
Bit 2 of word 100
March 19, 2010