beautypg.com

ProSoft Technology 5201-DFNT-104S User Manual

Page 37

background image

Configure the Gateway

104S v2 ♦ ProLinx Gateway

Protocol Manual

(Firmware v2.xx)


ProSoft Technology, Inc.

Page 37 of 157

March 19, 2010

If the highest bit (bit 31) is set, data will be produced by the driver for the
specified point at the rate set for periodic data generation. Bit 30 (0x40000000)
enables scanning of this point for event generation. If the bit is clear and the data
type is set for scanning, events will be generated for the point. If the bit is set,
events will not be generated for the point. This feature can be used to select
which points will generate events for the controlling station and can get rid of
event data that is not important to the application.