IEC-60870-5-104 (104S) Protocol Implementation
104S v2 ♦ ProLinx Gateway
Protocol Manual
(Firmware v2.xx)
ProSoft Technology, Inc.
Page 55 of 157
Freeze Start Type
The Freeze Start Type parameter will define when the gateway starts sending
the M_IT messages.
Example I - Freeze Start Type
If the gateway powers up with the following date and time clock:
03/25/2004 18:07:42
If you configure the Interval For Freeze parameter as follows:
The gateway would send the counter messages every 15 seconds. The gateway
would start sending the messages depending on the Freeze Start Type
parameter as follows:
Freeze Start Type
Time to Start Sending Messages
D 03/26/2004
00:00:00
H 03/25/2004
19:00:00
M 03/25/2004
18:08:00