Monitor points addressing, M_sp_na – ProSoft Technology 5201-DFNT-104S User Manual
Page 57

IEC-60870-5-104 (104S) Protocol Implementation
104S v2 ♦ ProLinx Gateway
Protocol Manual
(Firmware v2.xx)
ProSoft Technology, Inc.
Page 57 of 157
3.3.2 Monitor Points Addressing
As discussed before, the monitor points must be configured in a database area in
the 104S v2 gateway.
The monitor data types are described in the following table.
Data Type
Data Size
Addressing Type
M_SP_NA 1
bit
Bit
M_DP_NA 2
bits
Bit
M_ST_NA 1
byte
Byte
M_ME_NA 1
word
Word
M_ME_NB 1
word
Word
M_ME_NC 2
word
Double-Word
M_IT_NA 2
word
Double-Word
M_SP_NA
A Monitored Single-Point occupies one binary bit and uses bit-addressing. For
example, if you configured the following points as shown:
The following table describes how these points would be stored in the gateway
memory database.
Inf. Object Address
Gateway Database Address
100
Bit 0 of word 100 (Bit address 1600)
101
Bit 1 of word 100 (Bit address 1601)
102
Bit 2 of word 100 (Bit address 1602)
March 19, 2010