Command qualifiers – ProSoft Technology 5201-DFNT-104S User Manual
Page 126

104S v2 ♦ ProLinx Gateway
Reference
(Firmware v2.xx)
Protocol Manual
Page 126 of 157
ProSoft Technology, Inc.
March 19, 2010
Status Register Name
Description
10254
Host IP Address
(socket 1)
IP address of the client connected to the server.
…
10263
10264
StartDT active (socket 1)
This word contains the current StartDT state as
follows:
0 = The gateway has not received the most recent
STARTDT request through this socket or there has
been no communication with the remote host unit.
1 = The gateway has received the most recent
STARTDT request through this socket (therefore
will be reporting data to the remote client
connected through this socket).
10223
No Valid Data (socket 1)
Not Used.
…
10299
5.5
Command Qualifiers
Qualifier Code
Description
0
No additional definitions (Module will use Long duration pulse for this qualifier
selection).
1
Short pulse duration (circuit breaker), determined by user-set parameter in
gateway. This is supported in the gateway for single and dual point commands.
2
Long duration pulse (control relay), duration determined by user-set parameter
in gateway. This is supported in the gateway for single and dual point
commands.
3
Persistent output of control. This is supported in the gateway for all output data
types.
4 to 8
Reserved for standard definitions of standard - NOT SUPPORTED
9 to 15
Reserved for the selection of other predefined functions - NOT SUPPORTED
16 to 31
Reserved for special use (private range) - NOT SUPPORTED