3.7
Communication Error Codes
3.7.1 General Command Errors
Error
Code
Name
Description
1
Device not defined
The IED slave address referenced in the
command is not defined in the module. Check
to make sure there is an entry in the slave
table for each slave device referenced in the
command list.
2
Invalid command
This command is not valid. Check to make
sure the slave address parameter is greater
than or equal to zero and that the point count
is not set to zero.
3
Object not supported
The data object in the command is not
supported by the module. Refer to the DNP
subset for the Master Port.
4
Command function not supported
The function specified in the command is not
supported for the object type selected. Refer to
the DNP subset for the Master Port.
5
Command variation not supported
The variation specified in the command is not
supported for the object type selected.
6
Object 10 not enabled
The command is not supported unless Binary
Output Status is enabled
7
Object 40 not enabled
The command is not supported unless Analog
Output Status is enabled
8
Invalid time/date poll command
This time/date object poll command is not
valid.
9
Time/date poll command cannot
execute
This time/date object poll command cannot
execute because the module's clock has not
been synced from a valid source (from PLC or
connected Client)