ProSoft Technology MVI56E-DNPNET User Manual
Page 126

Contents
MVI56E-DNPNET ♦ ControlLogix Platform
User Manual
DNPNET Ethernet Client/Server Communication Module
Page 126 of 140
ProSoft Technology, Inc.
February 13, 2015
OBJECT
REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
3
32-Bit Analog Input
Without Flag
1
06
129, 130 00, 01
32
Server will return this
variation
4
16-Bit Analog Input
Without Flag
1
06
129, 130 00, 01
16
Server will return this
variation
5
Short Floating Point
Analog Input
1
06
129, 130 00, 01
40
Server will return this
variation
6
Long Floating Point
Analog Input
1
06
129, 130 00, 01
72
Server will return this
variation
31 0
Frozen Analog Input -
All Variations
Server will return Unknown
Object to this request
1
32-Bit Frozen Analog
Input
40
Server will return Unknown
Object to this request
2
16-Bit Frozen Analog
Input
24
Server will return Unknown
Object to this request
3
32-Bit Frozen Analog
Input With Time To
Freeze
88
Server will return Unknown
Object to this request
4
16-Bit Frozen Analog
Input With Time To
Freeze
72
Server will return Unknown
Object to this request
5
32-Bit Frozen Analog
Input Without Flag
32
Server will return Unknown
Object to this request
6
16-Bit Frozen Analog
Input Without Flag
16
Server will return Unknown
Object to this request
7
Short Floating Point
Frozen Analog Input
40
Server will return Unknown
Object to this request
8
Long Floating Point
Frozen Analog Input
72
Server will return Unknown
Object to this request
32 0
Analog Change
Event - All Variations
1
06, 07,
08
24
Server will return variation 2
data
1
32-Bit Analog
Change Event
Without Time
1
06, 07,
08
129, 130 17, 28
40
Server will return this
variation
2
16-Bit Analog
Change Event
Without Time
1
06, 07,
08
129, 130 17, 28
24
Server will return this
variation
3
32-Bit Analog
Change Event With
Time
1
06, 07,
08
129, 130 17, 28
88
Server will return this
variation
4
16-Bit Analog
Change Event With
Time
1
06, 07,
08
129, 130 17, 28
72
Server will return this
variation
5
Short Floating Point
Analog Change
Event
1
06, 07,
08
129, 130 17, 28
40
Server will return this