Word Offset
in Block
Data Field(s)
Description
1 to 247
Not Used
Not Used
The module responds to the request with a read block 9970 with the following format.
Word Offset
in Block
Data Field(s)
Description
0
Reserved
Reserved
1
Block Write ID
This is the next block requested by the module.
2
Year
This field contains the four-digit year for the new time value.
3
Month
This field contains the month value for the new time. Valid
entry for this field is in the range of 1 to 12.
4
Day
This field contains the day value for the new time. Valid entry
for this field is in the range of 1 to 31.
5
Hour
This field contains the hour value for the new time. Valid entry
for this field is in the range of 0 to 23.
6
Minute
This field contains the minute value for the new time. Valid
entry for this field is in the range of 0 to 59.
7
Seconds
This field contains the second value for the new time. Valid
entry for this field is in the range of 0 to 59.
8
Milliseconds
This field contains the millisecond value for the new time. Valid
entry for this field is in the range of 0 to 999.
9
Remote Time
Synchronization
This field informs the PLC if the date and time passed has
been synchronized with a remote DNP3 Ethernet Client device
on the module's server port.
1 = time has been set on the DNP3 Ethernet network.
0 = waiting for time sync from DNP3 Ethernet Client.
10 to 248
Not Used
Not Used
249
Block Read ID
This field contains the block identification code of 9970 for the
block.
Block 9971: Set Module Time From CLX Processor
Block identification code 9971 passes the clock time in the ControlLogix processsor to the
module. The date and time provided will be used to set the module's DNPNET clock.
Word Offset
in Block
Data Field(s)
Description
0
Block ID
This field contains the block identification code of 9971 for the
block.
1
Year
This field contains the four-digit year for the new time value.
2
Month
This field contains the month value for the new time. Valid
entry for this field is in the range of 1 to 12.
3
Day
This field contains the day value for the new time. Valid entry
for this field is in the range of 1 to 31.