2 dnpnet.data. controller tags – ProSoft Technology MVI56E-DNPNET User Manual
Page 116

Contents
MVI56E-DNPNET ♦ ControlLogix Platform
User Manual
DNPNET Ethernet Client/Server Communication Module
Page 116 of 140
ProSoft Technology, Inc.
February 13, 2015
Name
Data Type
Description
DNP3_Client
DNPNET_ENET_Client_type
Client configuration
IED_Database
DNPNET_IED_Database_type
Configure the Client database
sizes
DNP_List_Entry_Counts DNPNET_List_Entry_Counts_type
Lengths of the seven Overide
lists
DNP_Server_Binary_Inp
uts
DNPNET_BinIn_Class_Override_type[1
0]
Assigning classes to individual
points
DNP_Server_Analog16_I
nputs
DNPNET_A16in_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNP_Server_Analog32_I
nputs
DNPNET_A32in_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNP_Server_Float_Input
s
DNPNET_FLTin_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNP_Server_Double_Inp
uts
DNPNET_DBLin_ClassDeadband_Over
ride_type[10]
Assigning class/deadbands to
individual points
DNP_Server_List
DNPNET_Server_List_type[5]
List of servers the Client
connects to
DNP_Client_Commands DNPNET_Client_Commands[5]
List of commands the Client
sends to servers
IP_Settings
DNPNETETHERNETTYPE
IP Settings of module
4.4.2 DNPNET.DATA. controller tags
Name
Tag Name
Range
Description
DNP_Outputs DNPNET.DATA.DNP_Outp
uts.Binary
0 to 8000 points (500
16-bit words)
Object 12 binary INTs from
module’s server database
DNPNET.DATA.DNP_Outp
uts.Analog16
0 to 5000 points (if all
other DNP_Outputs are
0)
Object 41 analog INTs from
module’s server database
DNPNET.DATA.DNP_Outp
uts.Analog32
0 to 2500 points (if all
other DNP_Outputs are
0)
Object 41 analog DINTs from
module’s server database
DNPNET.DATA.DNP_Outp
uts.Float
0 to 2500 points (if all
other DNP_Outputs are
0)
Object 41 analog REALs
from module’s server
database
DNPNET.DATA.DNP_Outp
uts.Double
0 to 1250 points (if all
other DNP_Outputs are
0)
Object 41 analog double
precision floats from
module’s server database
DNP_Inputs
DNPNET.DATA.DNP_Input
s
.Binary
0 to 8000 points (‘500’
16-bit words)
Object 1 binary INTs for
module’s server database
DNPNET.DATA.DNP_Input
s.Analog16
0 to 5000 points (if all
other DNP_Inputs are
0)
Object 30 analog INTs for
module’s server database
DNPNET.DATA.DNP_Input
s.Analog32
0 to 2500 points (if all
other DNP_Inputs are
0)
Object 30 analog DINTs for
module’s server database