3diagnostics and troubleshooting – ProSoft Technology MVI56E-DNPNET User Manual
Page 45

MVI56E-DNPNET ♦ ControlLogix Platform
Contents
DNPNET Ethernet Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 45 of 140
February 13, 2015
3
Diagnostics and Troubleshooting
In This Chapter
Ethernet LED Indicators .........................................................................45
Clearing a Fault Condition .....................................................................47
Troubleshooting .....................................................................................47
Setting Up ProSoft Configuration Builder ...............................................48
Connecting Your PC to the Module .......................................................51
Using the Diagnostics Menu in ProSoft Configuration Builder ...............62
Communication Error Codes ..................................................................70
Connect to the Module’s Web Page ......................................................74
The module provides information on diagnostics and troubleshooting in the following forms:
LED status indicators on the front of the module provide information on the module’s
status.
Status data contained in the module can be viewed in ProSoft Configuration Builder
through the Ethernet port.
Status data values are transferred from the module to the processor.
3.1
Ethernet LED Indicators
The Ethernet LEDs indicate the module's Ethernet port status as follows:
LED
State
Description
Data
OFF
Ethernet connected at 10Mbps duplex speed
AMBER Solid Ethernet connected at 100Mbps duplex speed
Link
OFF
No physical network connection is detected. No Ethernet
communication is possible. Check wiring and cables.
GREEN Solid
or Blinking
Physical network connection detected. This LED must be ON solid
for Ethernet communication to be possible.
3.1.1 Scrolling LED Status Indicators
The scrolling LED display indicates the module’s operating status as follows:
Initialization Messages
Code
Message
Boot / DDOK
Module is initializing