ProSoft Technology MVI56E-DNPNET User Manual
Page 125

MVI56E-DNPNET ♦ ControlLogix Platform
Contents
DNPNET Ethernet Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 125 of 140
February 13, 2015
OBJECT
REQUEST
RESPONSE
Obj Var Description
Func
Codes
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
Data
Size
(bits)
NOTES
4
16-Bit Delta Counter
Change Event
Without Time
24
Server will return Unknown
Object to this request
5
32-Bit Counter
Change Event With
Time
88
Server will return Unknown
Object to this request
6
16-Bit Counter
Change Event With
Time
72
Server will return Unknown
Object to this request
7
32-Bit Delta Counter
Change Event With
Time
88
Server will return Unknown
Object to this request
8
16-Bit Delta Counter
Change Event With
Time
72
Server will return Unknown
Object to this request
23 0
Frozen Counter
Event - All Variations
Server will return Unknown
Object to this request
1
32-Bit Frozen
Counter Event
Without Time
40
Server will return Unknown
Object to this request
2
16-Bit Frozen
Counter Event
Without Time
24
Server will return Unknown
Object to this request
3
32-Bit Frozen Delta
Counter Event
Without Time
40
Server will return Unknown
Object to this request
4
16-Bit Frozen Delta
Counter Event
Without Time
24
Server will return Unknown
Object to this request
5
32-Bit Frozen
Counter Event With
Time
88
Server will return Unknown
Object to this request
6
16-Bit Frozen
Counter Event With
Time
72
Server will return Unknown
Object to this request
7
32-Bit Frozen Delta
Counter Event With
Time
88
Server will return Unknown
Object to this request
8
16-Bit Frozen Delta
Counter Event With
Time
72
Server will return Unknown
Object to this request
30 0
Analog Input - All
Variations
1
06
16
Server will respond with
variation 4 data
1
32-Bit Analog Input
1
06
129, 130 00, 01
40
Server will return this
variation
2
16-Bit Analog Input
1
06
129, 130 00, 01
24
Server will return this
variation