ProSoft Technology MVI56E-DNPNET User Manual

Page 16

background image

Contents

MVI56E-DNPNET ♦ ControlLogix Platform

User Manual

DNPNET Ethernet Client/Server Communication Module

Page 16 of 140

ProSoft Technology, Inc.

February 13, 2015

Parameter

Value

S

LOT

Enter the slot number in the rack where the MVI56E-DNPNET

module is located

I

NPUT

A

SSEMBLY

I

NSTANCE

1

I

NPUT

S

IZE

250

O

UTPUT

A

SSEMBLY

I

NSTANCE

2

O

UTPUT

S

IZE

248

C

ONFIGURATION

A

SSEMBLY

I

NSTANCE

4

C

ONFIGURATION

S

IZE

0

Important:

You must select the C

OMM

F

ORMAT

as D

ATA

-

INT

in the dialog box, otherwise the module will not

communicate over the backplane of the ControlLogix rack.

4

Click OK

to continue.

5

Edit the Module Properties.
Select the R

EQUESTED

P

ACKET

I

NTERVA

l value for scanning the I/O on the module. This

value represents the minimum frequency at which the module will handle scheduled

events. This value should not be set to less than 1 millisecond. The default value is 5

milliseconds. Values between 1 and 10 milliseconds should work with most applications.