ProSoft Technology MVI56E-DNPNET User Manual
Page 117

MVI56E-DNPNET ♦ ControlLogix Platform
Contents
DNPNET Ethernet Client/Server Communication Module
User Manual
ProSoft Technology, Inc.
Page 117 of 140
February 13, 2015
Name
Tag Name
Range
Description
DNPNET.DATA.DNP_Input
s.Float
0 to 2500 points (if all
other DNP_Inputs are
0)
Object 30 analog REALs for
module’s server database
DNPNET.DATA.DNP_Input
s.Double
0 to 1250 points (if all
other DNP_Inputs are
0)
Object 30 analog double
precision floats for module’s
server database
DNPNET.DATA.DNP_Input
s.Counter
0 to 1000 points
Object 20 counter DINTs for
module’s server database
IED_Outputs DNPNET.DATA.IED_Outpu
ts.Binary
0 to 8000 points (500
16-bit words)
Object 12 binary INTs for
module’s client database
DNPNET.DATA.IED_Outpu
ts.Analog16
0 to 20000 points (if all
other IED_Outputs are
0)
Object 41 analog INTs for
module’s client database
DNPNET.DATA.IED_Outpu
ts.Analog32
0 to 10000 points (if all
other IED_Outputs are
0)
Object 41 analog DINTs for
module’s client database
DNPNET.DATA.IED_Outpu
ts.Float
0 to 10000 points (if all
other IED_Outputs are
0)
Object 41 REALs for
module’s client database
IED_Inputs
DNPNET.DATA.IED_Inputs
.
Binary
0 to 8000 points (‘500’
16-bit words)
Object 1 binary INTs from
module’s client database
DNPNET.DATA.IED_Inputs
.
Analog16
0 to 20000 points (if all
other IED_Inputs are 0)
Object 30 analog INTs from
module’s client database
DNPNET.DATA.IED_Inputs
.
Analog32
0 to 10000 points (if all
other IED_Inputs are 0)
Object 30 analog DINTs from
module’s client database
DNPNET.DATA.IED_Inputs
.
Float
0 to 10000 points (if all
other IED_Inputs are 0)
Object 30 analog REALs
from module’s client
database
DNPNET.DATA.IED_Inputs
.
Counter
0 to 1000 points
Object 20 Counter DINTs
from module’s client
database
DNPNET.DATA.IED_Inputs
.
Binary_Out_Status
0 to 8000 points (‘500’
16-bit words)
Object 10 INTs output status
from module’s client
database
DNPNET.DATA.IED_Inputs
.
Analog16_Out_Status
0 to 20000 points
Object 10 INTs output status
from client’s database
DNPNET.DATA.IED_Inputs
.
Analog32_Out_Status
0 to 10000 points
Object 40 analog DINTs.
Output status from client’s
database
DNPNET.DATA.IED_Inputs
.
Float_Out_Status
0 to 10000 points
Object 40 analog REALs
output status from client’s
database