ProSoft Technology MVI56E-DNPNET User Manual
Page 32

Contents
MVI56E-DNPNET ♦ ControlLogix Platform
User Manual
DNPNET Ethernet Client/Server Communication Module
Page 32 of 140
ProSoft Technology, Inc.
February 13, 2015
Tag Name
Range
Description
DNPNET.CONFIG.DNP3_Ser
ver.Analog16_Input_Class
0 to 3
This parameter specifies the default class to
be utilized for all the 16-bit analog input points
in the DNP database that are not defined in
the override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Analog32_Input_Class
0 to 3
This parameter specifies the default class to
be utilized for all the 32-bit analog input points
in the DNP database that are not defined in
the override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Float_Class
0 to 3
This parameter specifies the default class to
be utilized for all the float input points in the
DNP database that are not defined in the
override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Double_Class
0 to 3
This parameter specifies the default class to
be utilized for all the double input points in the
DNP database that are not defined in the
override list section.
DNPNET.CONFIG.DNP3_Ser
ver.Analog16_Input_Deadban
d
0 to 32767
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the 16-bit analog input point
type in the DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.Analog32_Input_Deadban
d
0 to
2,147,483,647
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the 32-bit analog input point
type in the DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.Float_Deadband
0 to maximum
float value
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the float input point type in the
DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.Double_Deadband
0 to maximum
double value
This parameter specifies the default deadband
value assigned to all points not defined in the
override list for the double input point type in
the DNP database.
DNPNET.CONFIG.DNP3_Ser
ver.SelectOperate_Arm_Time
1 to 32767
Time period after select command received in
which operate command will be performed.
After the select command is received, the
operate command will only be honored if it
arrives within this period of time.
DNPNET.CONFIG.DNP3_Ser
ver.Write_Time_Interval
0 to 1440
minutes
Time interval to set the need time IIN bit
(0=never), which will cause the client to write
the time. Stored in milliseconds in the module
memory.
DNPNET.CONFIG.DNP3_Ser
ver.Spare1_Always_0
0,1, or 2 (Coded
Value)
IED can request acknowledgement from client
station when sending data. The codes are as
follows: 0=Never, 1=Sometimes, 2=Always
DNPNET.CONFIG.DNP3_Ser
ver. Spare1_Always_1
1 to 32767
milliseconds
Time period to wait for client Data Link
confirmation of last frame sent. This time is in
milliseconds. This parameter is only used if the
frame is sent with confirmation requested.